Wind turbine MV collector cable · 70 mm²
Ordering reference Wind turbine MV collector cable · 70 mm²
IEC 60502-2 / wind collector reference
Wind turbine MV collector cable
Application
Wind farm collectors · Turbine step-up feeders · Substation links · Renewable energy grids
Construction
- 1ConductorClass 2 copper or aluminium MV conductor · 19 × Ø2.17 mm · IEC 60228 cl.2
- 2Conductor screenSemi-conducting layer
- 3InsulationFlexible core insulation selected by motion duty
- 4Insulation screenSemi-conducting layer
- 5Metallic screenCopper wire screen (CWS)
- 6SheathUV, water and abrasion resistant PE / LSZH outer sheath
Technical parameters
Motion dutyFixed collector feeder from turbine to substation
Cable functionMedium-voltage wind farm collector circuit
Voltage class6.35/11 kV to 19/33 kV
Element designsingle core
Conductor / element size70 mm²
Conductor constructionClass 2 copper or aluminium MV conductor
Screen / protectionConductor screen, insulation screen and copper wire/tape metallic screen
JacketUV, water and abrasion resistant PE / LSZH outer sheath
Torsion ratingFixed buried or ducted collector route
Temperature class-25 °C to +90 °C conductor route guide
OD guide29.4 mm
Weight guide5445 kg/km
Conductor materialClass 2 copper or aluminium MV conductor
Bend radius15 x OD during installation
Max DC resistance at 20 °C0.440 Ω/km
Current rating (guide)≈ 226 A (Al, 1-core free air, 30 °C — IEC 60364-5-52 guide)
Routine test voltage21 kV a.c. (3.5 Uo, IEC 60502-2)
Ratings & materials
StandardIEC 60502-2 / wind collector reference
Voltage class6.35/11 kV to 19/33 kV
Temperature class-25 °C to +90 °C conductor route guide
UE Cable · China
sales@uecable.com
Confirm quantity, colour, printing, packing length, delivery country and required test documents when sending an enquiry.