Cable Specification Sheet IEC 61156-9 · Rev 01 · 2026-06

Cat8.1 S/FTP LAN · 4 x 2 pair

Ordering reference  Cat8.1 S/FTP LAN · 4 x 2 pair

IEC 61156-9 Cat8.1 S/FTP LAN

Application

Data-center switch links · High-speed server rooms · Short channel copper links · 25G and 40G cabling projects

1234
Indicative 4-pair construction — copper conductor, not to scale

Construction

  1. 1
    Conductor (per core)Bare copper conductor · 1 × Ø0.5 mm · IEC 60228 cl.1
  2. 2
    Pair insulationSolid PE or foam PE pair insulation
  3. 3
    FillerBedding / filler
  4. 4
    SheathPVC CMP plenum jacket

Technical parameters

CategoryCat8.1
Pair layout4 x 2 pair
ConductorAWG24/1 solid bare copper
Bandwidth2000 MHz
Transmission25GBASE-T / 40GBASE-T short channel design
ShieldingS/FTP
Jacket / ratingPVC CMP plenum jacket
Power supportPoE++ subject to channel and thermal design
Max DC resistance at 20 °C9.5 Ω/100 m max
OD guide9.0 mm
Operating temperature−15 °C to +90 °C
Cable weight103 kg/km
Bend radius4 x OD fixed
Mutual capacitance (nom.)≈ 52 pF/m (nominal)
Routine test voltage2.5 kV a.c. 5 min

Ratings & materials

StandardIEC 61156-9
UE Cable · China sales@uecable.com

Confirm quantity, colour, printing, packing length, delivery country and required test documents when sending an enquiry.

Request Quote