N2XH · 4C 6 mm²
Ordering reference N2XH · 4C 6 mm²
VDE 0276
N2XH
Application
Public buildings · Tunnels · Transport systems · Indoor fixed installation
Construction
- 1Conductor (per core)Copper conductor · 7 × Ø1.04 mm · IEC 60228 cl.2
- 2Core insulationXLPE
- 3FillerPP filler
- 4SheathLSZH
Technical parameters
Core layout4C
Conductor size6 mm²
ConductorCopper conductor
Max DC resistance at 20 °C3.08 Ω/km
OD guide23 mm
Operating temperature−40 °C to +90 °C
Cable weight0.36 kg/m
Bend radius6 x OD during installation
Outer sheathLSZH
Current rating (guide)≈ 51 A (Cu, multicore clipped, 30 °C — IEC 60364-5-52 guide)
Routine test voltage3.5 kV a.c. 5 min