Cable Specification Sheet VDE 0276 · Rev 01 · 2026-06

N2XH · 4C 2.5 mm²

Ordering reference  N2XH · 4C 2.5 mm²

VDE 0276 N2XH

Application

Public buildings · Tunnels · Transport systems · Indoor fixed installation

1234
Indicative 4-core construction — copper conductor, not to scale

Construction

  1. 1
    Conductor (per core)Copper conductor · 7 × Ø0.67 mm · IEC 60228 cl.2
  2. 2
    Core insulationXLPE
  3. 3
    FillerPP filler
  4. 4
    SheathLSZH

Technical parameters

Core layout4C
Conductor size2.5 mm²
ConductorCopper conductor
Max DC resistance at 20 °C7.41 Ω/km
OD guide21 mm
Operating temperature−40 °C to +90 °C
Cable weight0.21 kg/m
Bend radius6 x OD during installation
Outer sheathLSZH
Current rating (guide)≈ 30 A (Cu, multicore clipped, 30 °C — IEC 60364-5-52 guide)
Routine test voltage3.5 kV a.c. 5 min

Ratings & materials

StandardVDE 0276
Voltage class0.6/1 kV