Cable Specification Sheet IEC 60331 / EN 50288-7 · Rev 01 · 2026-06

Fire Resistant Instrumentation Mica LSZH SWA · 4 pair 1.5 mm²

Ordering reference  Fire Resistant Instrumentation Mica LSZH SWA · 4 pair 1.5 mm²

IEC 60331 / EN 50288-7 Fire Resistant Instrumentation Mica LSZH SWA

Application

Emergency shutdown circuits · Fire and gas systems · Offshore safety loops · Refinery shutdown systems

12345678
Indicative 4-pair construction — copper conductor · screened, not to scale

Construction

  1. 1
    Conductor (per core)Plain or tinned copper conductor · 7 × Ø0.52 mm · IEC 60228 cl.2
  2. 2
    Pair insulationXLPE, EPR or fire resistant insulation
  3. 3
    Individual screen (IS)Al/polyester foil + tinned-copper drain
  4. 4
    FillerBedding / filler
  5. 5
    Overall screen (OS)Al/polyester foil + drain
  6. 6
    BeddingPVC bedding
  7. 7
    ArmourGalvanised steel wire armour (SWA)
  8. 8
    SheathOrange or blue LSZH outer sheath

Technical parameters

Service packageSafety-critical instrumentation package
StandardIEC 60331 / EN 50288-7
Cable designMica fire barrier screened instrumentation cable
Voltage / signal class300/500 V
Pair / core design4 pair
Conductor / fibre1.5 mm²
Screen / protectionIndividual or overall screen with steel wire armour
Fire and safety ratingCircuit integrity fire resistant, LSZH and low smoke
Oil, mud and environmentEmergency shutdown, fire and gas, offshore safety circuits
SheathOrange or blue LSZH outer sheath
Electrical / optical reference12.1 Ω/km max
OD guide19.8 mm
Conductor materialPlain or tinned copper conductor
Operating temperature−15 °C to +90 °C (fire-rated)
Cable weight557 kg/km
Bend radius12 x OD during installation
Outer sheathOrange or blue LSZH outer sheath
Max DC resistance at 20 °C12.10 Ω/km
Mutual capacitance (nom.)≈ 120 pF/m core/core · 200 pF/m core/screen (nominal)
Routine test voltage2.0 kV a.c. 5 min

Ratings & materials

StandardIEC 60331 / EN 50288-7
Voltage class300/500 V