Cable Specification Sheet IEC 60331 / BS 7629-1 · Rev 01 · 2026-06

Fire And Gas Safety Circuit · 2 core 1.0 mm²

Ordering reference  Fire And Gas Safety Circuit · 2 core 1.0 mm²

IEC 60331 / BS 7629-1 Fire And Gas Safety Circuit

Application

Fire and gas detection · Emergency alarms · Evacuation systems · Safety instrumented systems

1234567
Indicative 2-pair construction — copper conductor · screened, not to scale

Construction

  1. 1
    Conductor (per core)Plain or tinned copper conductor · 7 × Ø0.43 mm · IEC 60228 cl.2
  2. 2
    Pair insulationXLPE, EPR or fire resistant insulation
  3. 3
    FillerBedding / filler
  4. 4
    Overall screen (OS)Al/polyester foil + drain
  5. 5
    BeddingPVC bedding
  6. 6
    ArmourGalvanised steel wire armour (SWA)
  7. 7
    SheathRed or orange LSZH outer sheath

Technical parameters

Service packageFire and gas alarm and safety package
StandardIEC 60331 / BS 7629-1
Cable designFire resistant screened alarm and safety cable
Voltage / signal class300/500 V
Pair / core design2 core
Conductor / fibre1.0 mm²
Screen / protectionFoil screen with drain wire and optional armour
Fire and safety ratingCircuit integrity, LSZH and low smoke
Oil, mud and environmentFire and gas detection, emergency alarm and evacuation circuits
SheathRed or orange LSZH outer sheath
Electrical / optical reference18.1 Ω/km max
OD guide20.5 mm
Conductor materialPlain or tinned copper conductor
Operating temperature−15 °C to +90 °C (fire-rated)
Cable weight543 kg/km
Bend radius12 x OD during installation
Outer sheathRed or orange LSZH outer sheath
Max DC resistance at 20 °C18.10 Ω/km
Mutual capacitance (nom.)≈ 120 pF/m core/core · 200 pF/m core/screen (nominal)
Routine test voltage3.5 kV a.c. 5 min

Ratings & materials

StandardIEC 60331 / BS 7629-1
Voltage class300/500 V
UE Cable · China sales@uecable.com

Confirm quantity, colour, printing, packing length, delivery country and required test documents when sending an enquiry.

Request Quote