Cable Specification Sheet NEK 606 · Rev 01 · 2026-06

BFOU · 0.75 mm²

Ordering reference  BFOU · 0.75 mm²

NEK 606 BFOU

Application

Emergency systems · Fire and gas systems · Offshore process control · Critical platform circuits

123456
Indicative 8-pair construction — copper conductor · screened, not to scale

Construction

  1. 1
    Conductor (per core)0.75 mm² · 24 × Ø0.2 mm · IEC 60228 cl.5
  2. 2
    Pair insulationMica fire barrier with EPR or HEPR insulation
  3. 3
    Individual screen (IS)Al/polyester foil + tinned-copper drain
  4. 4
    FillerBedding / filler
  5. 5
    Overall screen (OS)Al/polyester foil + drain
  6. 6
    SheathSHF2 or mud-resistant offshore sheath

Technical parameters

Circuit typeInstrumentation
Core / pair design8 pair
Conductor size0.75 mm²
Voltage class250 V, 0.6/1 kV or customer-specified offshore rating
Fire / mud behaviorFire resistant, flame retardant, low smoke and halogen-free construction
OD guide24 mm
Operating temperature−15 °C to +90 °C (fire-rated)
Cable weight0.39 kg/m
Bend radius8 x OD to 12 x OD during installation
Outer sheathSHF2 or mud-resistant offshore sheath
Max DC resistance at 20 °C24.50 Ω/km
Mutual capacitance (nom.)≈ 120 pF/m core/core · 200 pF/m core/screen (nominal)
Routine test voltage3.5 kV a.c. 5 min

Ratings & materials

StandardNEK 606
Voltage class250 V, 0.6/1 kV or customer-specified offshore rating