Programmable resettable analogue LHD cable
Ordering reference Programmable resettable analogue LHD cable
EN 54-28 analogue LHD reference
Programmable resettable analogue LHD cable
Application
Tunnels · Car parks · Solar PV routes · Cable galleries
Construction
- 1Conductor (per core)Four-core resistance-based temperature sensing cable
- 2Core insulationHeat-sensitive polymer sensor layer
- 3FillerPP filler
- 4ShieldBraid shield (C)
- 5SheathUV resistant polymer outer jacket
Technical parameters
Alarm temperature70 °C / 158 F
Detector typeProgrammable analogue resettable linear heat detector
Sensor constructionFour-core resistance-based temperature sensing cable
Jacket materialUV resistant polymer outer jacket
ProtectionStandard jacket or stainless steel braid option
EnvironmentTunnels, car parks, solar PV routes, cable galleries and critical equipment monitoring
Controller interfaceDedicated analogue LHD controller with pre-alarm, alarm and fault outputs
Zone length guideUp to 500 m per controller zone
OD guide7.4 mm
Conductor materialFour-core resistance-based temperature sensing cable
Cable weight104 kg/km
Bend radius10 x OD fixed guide
Routine test voltage2.5 kV a.c. 5 min
Ratings & materials
StandardEN 54-28 analogue LHD reference
Temperature class70 °C / 158 F, 85 °C / 185 F, 100 °C / 212 F, 120 °C / 248 F, 130 °C / 266 F
UE Cable · China
sales@uecable.com
Confirm quantity, colour, printing, packing length, delivery country and required test documents when sending an enquiry.