Products产品中心 Standards标准库 Industries应用行业 Insights资讯 Generator线缆生成器 About关于我们
Request a Quote索取报价
← Back to Fixed Temperature Nylon Linear Heat Detection Cable
Cable Specification Sheet Linear heat detection cable reference · Rev 01 · 2026-06

Fixed temperature nylon LHD cable

Ordering reference  Fixed temperature nylon LHD cable

Linear heat detection cable reference Fixed temperature nylon LHD cable

Application

Outdoor plant · Conveyors · Cooling towers · Moisture-exposed fire detection

1234
Indicative 2-core construction — copper conductor, not to scale

Construction

  1. 1
    Conductor (per core)Two low-resistance steel spring conductors separated by heat-sensitive polymer
  2. 2
    Core insulationHeat-sensitive polymer sensor layer
  3. 3
    FillerPP filler
  4. 4
    SheathNylon protective outer jacket

Technical parameters

Alarm temperature138 °C / 280 F
Detector typeDigital fixed-temperature linear heat detector
Sensor constructionTwo low-resistance steel spring conductors separated by heat-sensitive polymer
Jacket materialNylon protective outer jacket
ProtectionAbrasion, UV and chemical resistant outer jacket
EnvironmentOutdoor plant, conveyors, cable trays, cooling towers and moisture-exposed routes
Controller interfaceCompatible with conventional fire alarm input or addressable monitor module
Zone length guideUp to 300 m per monitored zone
OD guide4.7 mm
Conductor materialTwo low-resistance steel spring conductors separated by heat-sensitive polymer
Cable weight43 kg/km
Bend radius6 x OD fixed guide
Routine test voltage2.5 kV a.c. 5 min

Ratings & materials

StandardLinear heat detection cable reference
Temperature class68 °C / 154 F, 78 °C / 172 F, 88 °C / 190 F, 105 °C / 221 F, 138 °C / 280 F
UE Cable · China sales@uecable.com

Confirm quantity, colour, printing, packing length, delivery country and required test documents when sending an enquiry.