Cable Specification Sheet EN 50200 · Rev 01 · 2026-06

EN 50200 PH120 Fire Alarm · 3 core 2.5 mm²

Ordering reference  EN 50200 PH120 Fire Alarm · 3 core 2.5 mm²

EN 50200 EN 50200 PH120 Fire Alarm

Application

Emergency circuits · Fire alarm loops · Public buildings · Tunnels

12345
Indicative 3-core construction — copper conductor · screened, not to scale

Construction

  1. 1
    Conductor (per core)Copper conductor · 7 × Ø0.67 mm · IEC 60228 cl.2
  2. 2
    Core insulationLSZH fire resistant insulation
  3. 3
    FillerPP filler
  4. 4
    ShieldFoil shield (B)
  5. 5
    SheathLSZH

Technical parameters

Voltage class300/500 V
Core layout3 core
Conductor size2.5 mm²
Fire performancePH120 minimum 120 minutes at 840 °C
Protection / screenOptional foil screen
OD guide17 mm
Conductor materialCopper conductor
Operating temperature−15 °C to +90 °C (fire-rated)
Cable weight0.28 kg/m
Bend radius6 x OD during installation
Outer sheathLSZH
Max DC resistance at 20 °C7.41 Ω/km
Current rating (guide)≈ 30 A (Cu, multicore clipped, 30 °C — IEC 60364-5-52 guide)
Routine test voltage2.0 kV a.c. 5 min

Ratings & materials

StandardEN 50200
Voltage class300/500 V
UE Cable · China sales@uecable.com

Confirm quantity, colour, printing, packing length, delivery country and required test documents when sending an enquiry.