Products产品中心 Standards标准库 Industries应用行业 Insights资讯 Generator线缆生成器 About关于我们
Request a Quote索取报价
← Back to Hard Drawn Bare Copper Class 2 Conductor
Cable Specification Sheet BS 7884 · Rev 01 · 2026-06

Hard drawn bare copper Class 2 conductor · 70 mm²

Ordering reference  Hard drawn bare copper Class 2 conductor · 70 mm²

BS 7884 Hard drawn bare copper Class 2 conductor

Application

Overhead line conductors · Earthing conductors on insulators · Distribution line connections · Lightning protection

Indicative bare stranded conductor — copper, not to scale

Construction

  1. 1
    ConductorHard drawn copper conductor · 19 × Ø2.17 mm · IEC 60228 cl.2

Technical parameters

Conductor size70 mm²
Stranding19 hard-drawn copper wires
Nominal diameter9.87 mm
Max DC resistance at 20 °C0.268 Ω/km
Rated strength guide18.9 kN
Weight guide623 kg/km
Standard referenceBS 7884 Class 2
Conductor materialHard drawn copper conductor
Bend radius20 x conductor diameter handling guide
Outer sheathHard drawn bare copper surface
Current rating (guide)≈ 184 A (Cu, multicore clipped, 30 °C — IEC 60364-5-52 guide)

Ratings & materials

StandardBS 7884
UE Cable · China sales@uecable.com

Confirm quantity, colour, printing, packing length, delivery country and required test documents when sending an enquiry.

Request Quote