Hard drawn bare copper Class 2 conductor · 120 mm²
Ordering reference Hard drawn bare copper Class 2 conductor · 120 mm²
BS 7884
Hard drawn bare copper Class 2 conductor
Application
Overhead line conductors · Earthing conductors on insulators · Distribution line connections · Lightning protection
Construction
- 1ConductorHard drawn copper conductor · 37 × Ø2.03 mm · IEC 60228 cl.2
Technical parameters
Conductor size120 mm²
Stranding37 hard-drawn copper wires
Nominal diameter12.9 mm
Max DC resistance at 20 °C0.153 Ω/km
Rated strength guide32.4 kN
Weight guide1068 kg/km
Standard referenceBS 7884 Class 2
Conductor materialHard drawn copper conductor
Bend radius20 x conductor diameter handling guide
Outer sheathHard drawn bare copper surface
Current rating (guide)≈ 259 A (Cu, multicore clipped, 30 °C — IEC 60364-5-52 guide)
Ratings & materials
StandardBS 7884
UE Cable · China
sales@uecable.com
Confirm quantity, colour, printing, packing length, delivery country and required test documents when sending an enquiry.