Products产品中心 Standards标准库 Industries应用行业 Insights资讯 Generator线缆生成器 About关于我们
Request a Quote索取报价
← Back to NF C 33-209 Service Aerial Bundled Cable
Cable Specification Sheet NF C 33-209 · Rev 01 · 2026-06

NF C 33-209 service ABC · 2 x phase + neutral messenger

Ordering reference  NF C 33-209 service ABC · 2 x phase + neutral messenger

NF C 33-209 NF C 33-209 service ABC

Application

Building service connections · Urban tributary networks · Rural service drops · Pole-to-building supply

12
Indicative 3-core construction — aluminium conductor, not to scale

Construction

  1. 1
    Conductor (per core)Class 2 stranded aluminium conductor
  2. 2
    Core insulationXLPE insulation for aerial service conductors · Wall XLPE insulation for aerial service conductors mm

Technical parameters

Voltage class0.6/1 kV
Bundle layout2 x phase + neutral messenger
Phase conductor70 mm² stranded aluminium phase conductor
Neutral / messenger70 mm² AAAC neutral messenger
InsulationXLPE insulation for aerial service conductors
Screen / supportNeutral messenger load-bearing bundle
Max DC resistance at 20 °C0.443 Ω/km
Bundle OD guide27 mm
Weight guide1.13 kg/m
Conductor materialClass 2 stranded aluminium conductor
Operating temperature−40 °C to +90 °C
Bend radius10 x OD during installation
Outer sheathBlack weather resistant XLPE surface
Routine test voltage3.5 kV a.c. 5 min

Ratings & materials

StandardNF C 33-209
Voltage class0.6/1 kV
UE Cable · China sales@uecable.com

Confirm quantity, colour, printing, packing length, delivery country and required test documents when sending an enquiry.

Request Quote