NF C 33-209 service ABC · 2 x phase + neutral messenger
Ordering reference NF C 33-209 service ABC · 2 x phase + neutral messenger
NF C 33-209
NF C 33-209 service ABC
Application
Building service connections · Urban tributary networks · Rural service drops · Pole-to-building supply
Construction
- 1Conductor (per core)Class 2 stranded aluminium conductor
- 2Core insulationXLPE insulation for aerial service conductors · Wall XLPE insulation for aerial service conductors mm
Technical parameters
Voltage class0.6/1 kV
Bundle layout2 x phase + neutral messenger
Phase conductor70 mm² stranded aluminium phase conductor
Neutral / messenger70 mm² AAAC neutral messenger
InsulationXLPE insulation for aerial service conductors
Screen / supportNeutral messenger load-bearing bundle
Max DC resistance at 20 °C0.443 Ω/km
Bundle OD guide27 mm
Weight guide1.13 kg/m
Conductor materialClass 2 stranded aluminium conductor
Operating temperature−40 °C to +90 °C
Bend radius10 x OD during installation
Outer sheathBlack weather resistant XLPE surface
Routine test voltage3.5 kV a.c. 5 min
Ratings & materials
StandardNF C 33-209
Voltage class0.6/1 kV
UE Cable · China
sales@uecable.com