IEC 60502-2 screened MV ABC 19/33 kV · 3 phase + support conductor
Ordering reference IEC 60502-2 screened MV ABC 19/33 kV · 3 phase + support conductor
IEC 60502-2
IEC 60502-2 screened MV ABC 19/33 kV
Application
33 kV overhead distribution · Utility feeders · Rural MV networks · Substation overhead exits
Construction
- 1Conductor (per core)Class 2 stranded aluminium conductor
- 2Core insulationXLPE insulation with semi-conductive screens · Wall XLPE insulation with semi-conductive screens mm
- 3ShieldFoil shield (B)
Technical parameters
Voltage class19/33 kV
Bundle layout3 phase + support conductor
Phase conductor50 mm² stranded aluminium phase conductor
Neutral / messenger25 mm² galvanised steel support conductor
InsulationXLPE insulation with semi-conductive screens
Screen / supportCopper wire or copper tape metallic screen
Max DC resistance at 20 °C0.641 Ω/km
Bundle OD guide66 mm
Weight guide3.07 kg/m
Conductor materialClass 2 stranded aluminium conductor
Operating temperature−40 °C to +90 °C
Bend radius15 x OD during installation
Outer sheathBlack HDPE outer sheath
Routine test voltage66.5 kV a.c. (3.5 Uo, IEC 60502-2)
Ratings & materials
StandardIEC 60502-2
Voltage class19/33 kV
UE Cable · China
sales@uecable.com
Confirm quantity, colour, printing, packing length, delivery country and required test documents when sending an enquiry.