Products产品中心 Standards标准库 Industries应用行业 Insights资讯 Generator线缆生成器 About关于我们
Request a Quote索取报价
← Back to AS/NZS 3560 LV Aerial Bundled Cable
Cable Specification Sheet AS/NZS 3560 Part 1 · Rev 01 · 2026-06

AS/NZS 3560 LV ABC · 4 core LV ABC

Ordering reference  AS/NZS 3560 LV ABC · 4 core LV ABC

AS/NZS 3560 Part 1 AS/NZS 3560 LV ABC

Application

Utility LV networks · Service drops · Rural lines · Street lighting circuits

12
Indicative 4-core construction — aluminium conductor, not to scale

Construction

  1. 1
    Conductor (per core)Class 2 stranded aluminium conductor
  2. 2
    Core insulationUV stabilised XLPE insulation with rib identification · Wall UV stabilised XLPE insulation with rib identification mm

Technical parameters

Voltage class0.6/1 kV
Bundle layout4 core LV ABC
Phase conductor50 mm² stranded aluminium phase conductor
Neutral / messenger50 mm² insulated aluminium neutral
InsulationUV stabilised XLPE insulation with rib identification
Screen / supportSelf-supporting bundled construction
Max DC resistance at 20 °C0.641 Ω/km
Bundle OD guide26 mm
Weight guide1.44 kg/m
Conductor materialClass 2 stranded aluminium conductor
Operating temperature−40 °C to +90 °C
Bend radius10 x OD during installation
Outer sheathBlack UV resistant XLPE surface
Routine test voltage3.5 kV a.c. 5 min

Ratings & materials

StandardAS/NZS 3560 Part 1
Voltage class0.6/1 kV
UE Cable · China sales@uecable.com

Confirm quantity, colour, printing, packing length, delivery country and required test documents when sending an enquiry.