AS/NZS 3560 LV ABC · 2 core LV ABC
Ordering reference AS/NZS 3560 LV ABC · 2 core LV ABC
AS/NZS 3560 Part 1
AS/NZS 3560 LV ABC
Application
Utility LV networks · Service drops · Rural lines · Street lighting circuits
Construction
- 1Conductor (per core)Class 2 stranded aluminium conductor
- 2Core insulationUV stabilised XLPE insulation with rib identification · Wall UV stabilised XLPE insulation with rib identification mm
Technical parameters
Voltage class0.6/1 kV
Bundle layout2 core LV ABC
Phase conductor35 mm² stranded aluminium phase conductor
Neutral / messenger25 mm² insulated aluminium neutral
InsulationUV stabilised XLPE insulation with rib identification
Screen / supportSelf-supporting bundled construction
Max DC resistance at 20 °C0.868 Ω/km
Bundle OD guide24 mm
Weight guide0.68 kg/m
Conductor materialClass 2 stranded aluminium conductor
Operating temperature−40 °C to +90 °C
Bend radius10 x OD during installation
Outer sheathBlack UV resistant XLPE surface
Routine test voltage3.5 kV a.c. 5 min
Ratings & materials
StandardAS/NZS 3560 Part 1
Voltage class0.6/1 kV
UE Cable · China
sales@uecable.com