Cable Specification Sheet UL 1277 TC-ER / WTTC reference · Rev 01 · 2026-06

VFD tray cable · 4 core 10 AWG / 5.26 mm²

Ordering reference  VFD tray cable · 4 core 10 AWG / 5.26 mm²

UL 1277 TC-ER / WTTC reference VFD tray cable

Application

VFD drives · Motor feeds · Industrial automation · Pumps and fans

12345
Indicative 4-core construction — copper conductor · screened, not to scale

Construction

  1. 1
    Conductor (per core)Fine stranded bare copper conductor · 84 × Ø0.28 mm · IEC 60228 cl.5
  2. 2
    Core insulationXLPE or PVC nylon VFD insulation
  3. 3
    FillerPP filler
  4. 4
    ShieldBraid shield (C)
  5. 5
    SheathOil and sunlight resistant PVC tray jacket

Technical parameters

Tray cable dutyVFD motor tray feed
Circuit typeVFD motor feed
Core / pair design4 core
Conductor size10 AWG / 5.26 mm²
Voltage class600 V / 1000 V
Max DC resistance at 20 °C3.52 Ω/km
OD guide17.9 mm
Conductor materialFine stranded bare copper conductor
Operating temperature−40 °C to +90 °C
Cable weight0.67 kg/m
Bend radius8 x OD fixed guide
Outer sheathOil and sunlight resistant PVC tray jacket
Current rating (guide)≈ 51 A (Cu, multicore clipped, 30 °C — IEC 60364-5-52 guide)
Routine test voltage2.5 kV a.c. 5 min

Ratings & materials

StandardUL 1277 TC-ER / WTTC reference
Voltage class600 V / 1000 V
Temperature class90 °C dry / 75 °C wet guide