Products产品中心 Standards标准库 Industries应用行业 Insights资讯 Generator线缆生成器 About关于我们
Request a Quote索取报价
← Back to TC-ER Exposed Run Tray Cable
Cable Specification Sheet UL 1277 TC-ER · Rev 01 · 2026-06

TC-ER · 3 core 14 AWG / 2.08 mm²

Ordering reference  TC-ER · 3 core 14 AWG / 2.08 mm²

UL 1277 TC-ER TC-ER

Application

Industrial machinery · Plant engineering · Cable tray exposed runs · Control panels

1234
Indicative 3-core construction — copper conductor, not to scale

Construction

  1. 1
    Conductor (per core)Fine stranded bare copper conductor · 50 × Ø0.23 mm · IEC 60228 cl.5
  2. 2
    Core insulationPVC nylon insulation
  3. 3
    FillerPP filler
  4. 4
    SheathOil, sunlight and crush resistant PVC tray jacket

Technical parameters

Tray cable dutyExposed-run power and control tray
Circuit typePower and control
Core / pair design3 core
Conductor size14 AWG / 2.08 mm²
Voltage class600 V
Max DC resistance at 20 °C8.89 Ω/km
OD guide13.1 mm
Conductor materialFine stranded bare copper conductor
Operating temperature−15 °C to +70 °C
Cable weight0.33 kg/m
Bend radius6 x OD fixed guide
Outer sheathOil, sunlight and crush resistant PVC tray jacket
Current rating (guide)≈ 24 A (Cu, multicore clipped, 30 °C — IEC 60364-5-52 guide)
Routine test voltage2.5 kV a.c. 5 min

Ratings & materials

StandardUL 1277 TC-ER
Voltage class600 V
Temperature class90 °C dry / 75 °C wet guide
UE Cable · China sales@uecable.com

Confirm quantity, colour, printing, packing length, delivery country and required test documents when sending an enquiry.