N2XSY · Single core 300 mm²
Ordering reference N2XSY · Single core 300 mm²
IEC 60502-2
N2XSY
Application
Distribution networks · Transformer stations · Switching blocks · Power plants
Construction
- 1ConductorCopper conductor · 37 × Ø3.21 mm · IEC 60228 cl.2
- 2Conductor screenSemi-conducting layer
- 3InsulationXLPE
- 4Insulation screenSemi-conducting layer
- 5Metallic screenCopper wire screen (CWS)
- 6SheathPVC
Technical parameters
Voltage class6/10 kV
Cross-section300 mm²
Max DC resistance at 20 °C0.0601 Ω/km
Metallic screen25 mm² copper wire screen
OD guide51 mm
Core layoutSingle core
Conductor materialCopper conductor
Operating temperature−40 °C to +90 °C
Cable weight5.3 kg/m
Bend radius20 x OD during installation
Outer sheathPVC
Current rating (guide)≈ 741 A (Cu, 1-core free air, 30 °C — IEC 60364-5-52 guide)
Routine test voltage21 kV a.c. (3.5 Uo, IEC 60502-2)
Ratings & materials
StandardIEC 60502-2
Voltage class6/10 kV
UE Cable · China
sales@uecable.com
Confirm quantity, colour, printing, packing length, delivery country and required test documents when sending an enquiry.