Cable Specification Sheet IEC 60502-1 · Rev 01 · 2026-06

IEC 60502-1 XLPE/PVC · 4C 150 mm²

Ordering reference  IEC 60502-1 XLPE/PVC · 4C 150 mm²

IEC 60502-1 IEC 60502-1 XLPE/PVC

Application

Power distribution · Industrial plants · Building feeders · Infrastructure circuits

1234
Indicative 4-core construction — aluminium conductor, not to scale

Construction

  1. 1
    Conductor (per core)Aluminium conductor · 37 × Ø2.27 mm · IEC 60228 cl.2
  2. 2
    Core insulationXLPE
  3. 3
    FillerPP filler
  4. 4
    SheathPVC

Technical parameters

Core layout4C
Conductor size150 mm²
ConductorAluminium conductor
Max DC resistance at 20 °C0.206 Ω/km
OD guide43 mm
Operating temperature−40 °C to +90 °C
Cable weight2.80 kg/m
Bend radius6 x OD during installation
Outer sheathPVC
Current rating (guide)≈ 296 A (Al, multicore clipped, 30 °C — IEC 60364-5-52 guide)
Routine test voltage3.5 kV a.c. 5 min

Ratings & materials

StandardIEC 60502-1
Voltage class0.6/1 kV
UE Cable · China sales@uecable.com

Confirm quantity, colour, printing, packing length, delivery country and required test documents when sending an enquiry.