Cable Specification Sheet BS 6622 · Rev 01 · 2026-06

BS 6622 XLPE/AWA/SWA/PVC · Three core 240 mm²

Ordering reference  BS 6622 XLPE/AWA/SWA/PVC · Three core 240 mm²

BS 6622 BS 6622 XLPE/AWA/SWA/PVC

Application

UK-style MV distribution · Substations · Industrial feeders · Direct burial

1234567
Indicative medium-voltage 3-core construction — copper conductor · screened, not to scale

Construction

  1. 1
    Conductor (per core)Copper conductor · 37 × Ø2.87 mm · IEC 60228 cl.2
  2. 2
    Core insulationXLPE
  3. 3
    FillerPP filler
  4. 4
    ShieldFoil shield (B)
  5. 5
    BeddingPVC bedding
  6. 6
    ArmourGalvanised steel wire armour (SWA)
  7. 7
    SheathPVC

Technical parameters

Voltage class8.7/15 kV
Cross-section240 mm²
Max DC resistance at 20 °C0.0754 Ω/km
Metallic screen25 mm² copper wire screen
OD guide72 mm
Core layoutThree core
Conductor materialCopper conductor
Operating temperature−40 °C to +90 °C
Cable weight10.7 kg/m
Bend radius15 x OD during installation
Outer sheathPVC
Current rating (guide)≈ 514 A (Cu, multicore clipped, 30 °C — IEC 60364-5-52 guide)
Routine test voltage30.5 kV a.c. (3.5 Uo, IEC 60502-2)