Cable Specification Sheet BS 6622 · Rev 01 · 2026-06

BS 6622 XLPE/AWA/SWA/PVC · Single core 400 mm²

Ordering reference  BS 6622 XLPE/AWA/SWA/PVC · Single core 400 mm²

BS 6622 BS 6622 XLPE/AWA/SWA/PVC

Application

UK-style MV distribution · Substations · Industrial feeders · Direct burial

12345678
Indicative medium-voltage single-core construction — copper conductor · screened, not to scale

Construction

  1. 1
    ConductorCopper conductor · 53 × Ø3.1 mm · IEC 60228 cl.2
  2. 2
    Conductor screenSemi-conducting layer
  3. 3
    InsulationXLPE
  4. 4
    Insulation screenSemi-conducting layer
  5. 5
    Metallic screenCopper wire screen (CWS)
  6. 6
    BeddingPVC bedding
  7. 7
    ArmourAluminium / steel wire armour
  8. 8
    SheathPVC

Technical parameters

Voltage class3.6/6 kV
Cross-section400 mm²
Max DC resistance at 20 °C0.0470 Ω/km
Metallic screen35 mm² copper wire screen
OD guide56 mm
Core layoutSingle core
Conductor materialCopper conductor
Operating temperature−40 °C to +90 °C
Cable weight6.7 kg/m
Bend radius20 x OD during installation
Outer sheathPVC
Current rating (guide)≈ 820 A (Cu, 1-core free air, 30 °C — IEC 60364-5-52 guide)
Routine test voltage12.6 kV a.c. (3.5 Uo, IEC 60502-2)

Ratings & materials

StandardBS 6622
Voltage class3.6/6 kV
UE Cable · China sales@uecable.com

Confirm quantity, colour, printing, packing length, delivery country and required test documents when sending an enquiry.