IEC 60502-1 XLPE/PVC · 2C 185 mm²
Ordering reference IEC 60502-1 XLPE/PVC · 2C 185 mm²
IEC 60502-1
IEC 60502-1 XLPE/PVC
Application
Power distribution · Industrial plants · Building feeders · Infrastructure circuits
Construction
- 1Conductor (per core)Aluminium conductor · 37 × Ø2.52 mm · IEC 60228 cl.2
- 2Core insulationXLPE
- 3FillerPP filler
- 4SheathPVC
Technical parameters
Core layout2C
Conductor size185 mm²
ConductorAluminium conductor
Max DC resistance at 20 °C0.164 Ω/km
OD guide42 mm
Operating temperature−40 °C to +90 °C
Cable weight1.76 kg/m
Bend radius6 x OD during installation
Outer sheathPVC
Current rating (guide)≈ 339 A (Al, multicore clipped, 30 °C — IEC 60364-5-52 guide)
Routine test voltage3.5 kV a.c. 5 min
Ratings & materials
StandardIEC 60502-1
Voltage class0.6/1 kV
UE Cable · China
sales@uecable.com
Confirm quantity, colour, printing, packing length, delivery country and required test documents when sending an enquiry.