BS 7846 fire resistant power cable · 4C 50 mm²
Ordering reference BS 7846 fire resistant power cable · 4C 50 mm²
BS 7846
BS 7846 fire resistant power cable
Application
Emergency power · Life safety systems · Fire pumps · Critical infrastructure
Construction
- 1Conductor (per core)Copper conductor · 19 × Ø1.83 mm · IEC 60228 cl.2
- 2Core insulationMica fire barrier with XLPE insulation
- 3FillerPP filler
- 4BeddingPVC bedding
- 5ArmourGalvanised steel wire armour (SWA)
- 6SheathLSZH
Technical parameters
Core layout4C
Conductor size50 mm²
ConductorCopper conductor
Max DC resistance at 20 °C0.387 Ω/km
OD guide40 mm
Operating temperature−15 °C to +90 °C (fire-rated)
Cable weight2.70 kg/m
Bend radius12 x OD during installation
Outer sheathLSZH
Current rating (guide)≈ 180 A (Cu, multicore clipped, 30 °C — IEC 60364-5-52 guide)
Routine test voltage3.5 kV a.c. 5 min
Ratings & materials
StandardBS 7846
Voltage class0.6/1 kV
UE Cable · China
sales@uecable.com
Confirm quantity, colour, printing, packing length, delivery country and required test documents when sending an enquiry.