LSZH instrumentation cable · 8 pair 1.5 mm²
Ordering reference LSZH instrumentation cable · 8 pair 1.5 mm²
EN 50288-7
LSZH instrumentation cable
Application
Process control · Public infrastructure monitoring · Data centers · Transport control systems
Construction
- 1Conductor (per core)Copper conductor · 7 × Ø0.52 mm · IEC 60228 cl.2
- 2Pair insulationXLPE or LSZH-compatible instrumentation insulation
- 3Individual screen (IS)Al/polyester foil + tinned-copper drain
- 4FillerBedding / filler
- 5Overall screen (OS)Al/polyester foil + drain
- 6SheathLSZH outer sheath
Technical parameters
Voltage class300/500 V
Cable useInstrumentation signal
Core / pair design8 pair
Conductor size1.5 mm²
Max DC resistance at 20 °C12.1 Ω/km
Fire behaviorLow smoke, zero halogen instrumentation cable for enclosed routes
OD guide15 mm
Conductor materialCopper conductor
Operating temperature−40 °C to +90 °C
Cable weight0.33 kg/m
Bend radius6 x OD during installation
Outer sheathLSZH outer sheath
Mutual capacitance (nom.)≈ 120 pF/m core/core · 200 pF/m core/screen (nominal)
Routine test voltage2.0 kV a.c. 5 min
Ratings & materials
StandardEN 50288-7
Voltage class300/500 V
UE Cable · China
sales@uecable.com