Cable Specification Sheet EN 50288-7 · Rev 01 · 2026-06

LSZH instrumentation cable · 8 pair 0.5 mm²

Ordering reference  LSZH instrumentation cable · 8 pair 0.5 mm²

EN 50288-7 LSZH instrumentation cable

Application

Process control · Public infrastructure monitoring · Data centers · Transport control systems

123456
Indicative 8-pair construction — copper conductor · screened, not to scale

Construction

  1. 1
    Conductor (per core)Copper conductor · 7 × Ø0.3 mm · IEC 60228 cl.2
  2. 2
    Pair insulationXLPE or LSZH-compatible instrumentation insulation
  3. 3
    Individual screen (IS)Al/polyester foil + tinned-copper drain
  4. 4
    FillerBedding / filler
  5. 5
    Overall screen (OS)Al/polyester foil + drain
  6. 6
    SheathLSZH outer sheath

Technical parameters

Voltage class300/500 V
Cable useInstrumentation signal
Core / pair design8 pair
Conductor size0.5 mm²
Max DC resistance at 20 °C39.0 Ω/km
Fire behaviorLow smoke, zero halogen instrumentation cable for enclosed routes
OD guide14 mm
Conductor materialCopper conductor
Operating temperature−40 °C to +90 °C
Cable weight0.22 kg/m
Bend radius6 x OD during installation
Outer sheathLSZH outer sheath
Mutual capacitance (nom.)≈ 120 pF/m core/core · 200 pF/m core/screen (nominal)
Routine test voltage2.0 kV a.c. 5 min

Ratings & materials

StandardEN 50288-7
Voltage class300/500 V
UE Cable · China sales@uecable.com

Confirm quantity, colour, printing, packing length, delivery country and required test documents when sending an enquiry.