Cable Specification Sheet BS 7629-1 · Rev 01 · 2026-06

Fire resistant LSZH alarm cable · 3 core 1.0 mm²

Ordering reference  Fire resistant LSZH alarm cable · 3 core 1.0 mm²

BS 7629-1 Fire resistant LSZH alarm cable

Application

Fire alarms · Emergency lighting · Life safety circuits · Public building emergency systems

12345
Indicative 3-core construction — copper conductor · screened, not to scale

Construction

  1. 1
    Conductor (per core)Copper conductor · 7 × Ø0.43 mm · IEC 60228 cl.2
  2. 2
    Core insulationMica fire barrier with LSZH insulation
  3. 3
    FillerPP filler
  4. 4
    ShieldBraid shield (C)
  5. 5
    SheathLSZH outer sheath

Technical parameters

Voltage class300/500 V
Cable useFire alarm and emergency circuit
Core / pair design3 core
Conductor size1.0 mm²
Max DC resistance at 20 °CConfirm to IEC 60228
Fire behaviorFire resistant, low smoke and halogen-free emergency circuit construction
OD guide13 mm
Conductor materialCopper conductor
Operating temperature−15 °C to +90 °C (fire-rated)
Cable weight0.20 kg/m
Bend radius6 x OD during installation
Outer sheathLSZH outer sheath
Current rating (guide)≈ 22 A (Cu, multicore clipped, 30 °C — IEC 60364-5-52 guide)
Routine test voltage2.0 kV a.c. 5 min

Ratings & materials

StandardBS 7629-1
Voltage class300/500 V
UE Cable · China sales@uecable.com

Confirm quantity, colour, printing, packing length, delivery country and required test documents when sending an enquiry.