N2XY · 3C 25 mm²
Ordering reference N2XY · 3C 25 mm²
VDE 0276
N2XY
Application
Industrial power distribution · Building feeders · Cable ducts · Fixed installation
Construction
- 1Conductor (per core)Copper conductor · 7 × Ø2.13 mm · IEC 60228 cl.2
- 2Core insulationXLPE
- 3FillerPP filler
- 4SheathPVC
Technical parameters
Core layout3C
Conductor size25 mm²
ConductorCopper conductor
Max DC resistance at 20 °C0.727 Ω/km
OD guide25 mm
Operating temperature−40 °C to +90 °C
Cable weight0.92 kg/m
Bend radius6 x OD during installation
Outer sheathPVC
Current rating (guide)≈ 119 A (Cu, multicore clipped, 30 °C — IEC 60364-5-52 guide)
Routine test voltage3.5 kV a.c. 5 min
Ratings & materials
StandardVDE 0276
Voltage class0.6/1 kV
UE Cable · China