Products产品中心 Standards标准库 Industries应用行业 Insights资讯 Generator线缆生成器 About关于我们
Request a Quote索取报价
← Back to Mineral Insulated Copper Sheathed Fire Resistant Cable
Cable Specification Sheet IEC 60702 · Rev 01 · 2026-06

Mineral Insulated Copper Sheathed · 2 core 1.0 mm²

Ordering reference  Mineral Insulated Copper Sheathed · 2 core 1.0 mm²

IEC 60702 Mineral Insulated Copper Sheathed

Application

Fire alarm circuits · Emergency lighting · Oil and gas safety circuits · High temperature fixed wiring

1234
Indicative 2-core construction — copper conductor, not to scale

Construction

  1. 1
    Conductor (per core)Copper conductor · 7 × Ø0.43 mm · IEC 60228 cl.2
  2. 2
    Core insulationMineral insulation
  3. 3
    FillerPP filler
  4. 4
    SheathCopper sheath with optional LSZH oversheath

Technical parameters

Voltage class500/750 V
Core layout2 core
Conductor size1.0 mm²
Fire performanceInherent mineral insulated circuit integrity
Protection / screenCopper sheath
OD guide11 mm
Conductor materialCopper conductor
Operating temperature−15 °C to +90 °C (fire-rated)
Cable weight0.10 kg/m
Bend radius6 x OD during installation
Outer sheathCopper sheath with optional LSZH oversheath
Max DC resistance at 20 °C18.10 Ω/km
Current rating (guide)≈ 22 A (Cu, multicore clipped, 30 °C — IEC 60364-5-52 guide)
Routine test voltage2.5 kV a.c. 5 min

Ratings & materials

StandardIEC 60702
Voltage class500/750 V
UE Cable · China sales@uecable.com

Confirm quantity, colour, printing, packing length, delivery country and required test documents when sending an enquiry.

Request Quote