BS 7846 Fire Resistant Instrumentation · 20 pair 1.0 mm²
Ordering reference BS 7846 Fire Resistant Instrumentation · 20 pair 1.0 mm²
BS 7846
BS 7846 Fire Resistant Instrumentation
Application
Fire resistant instrumentation · Emergency control circuits · Safety system signals · Process safety
Construction
- 1Conductor (per core)Copper conductor · 7 × Ø0.43 mm · IEC 60228 cl.2
- 2Pair insulationFire resistant LSZH insulation
- 3FillerBedding / filler
- 4Overall screen (OS)Al/polyester foil + drain
- 5SheathLSZH
Technical parameters
Voltage class300/500 V
Core layout20 pair
Conductor size1.0 mm²
Fire performanceIEC 60331 / BS 6387 circuit integrity
Protection / screenCollective metallic screen and drain wire
OD guide46 mm
Conductor materialCopper conductor
Operating temperature−15 °C to +90 °C (fire-rated)
Cable weight0.42 kg/m
Bend radius6 x OD during installation
Outer sheathLSZH
Max DC resistance at 20 °C18.10 Ω/km
Mutual capacitance (nom.)≈ 120 pF/m core/core · 200 pF/m core/screen (nominal)
Routine test voltage2.0 kV a.c. 5 min
Ratings & materials
StandardBS 7846
Voltage class300/500 V
UE Cable · China
sales@uecable.com
Confirm quantity, colour, printing, packing length, delivery country and required test documents when sending an enquiry.