Products产品中心 Standards标准库 Industries应用行业 Insights资讯 Generator线缆生成器 About关于我们
Request a Quote索取报价
← Back to LiYY Signal And Control Cable
Cable Specification Sheet VDE 0812 · Rev 01 · 2026-06

LiYY signal control cable · 7 core 0.75 mm²

Ordering reference  LiYY signal control cable · 7 core 0.75 mm²

VDE 0812 LiYY signal control cable

Application

Electronic control systems · Signal transmission · Panel wiring · Instrumentation auxiliaries

12345
Indicative 7-core construction — copper conductor · screened, not to scale

Construction

  1. 1
    Conductor (per core)Class 5 flexible copper conductor · 24 × Ø0.2 mm · IEC 60228 cl.5
  2. 2
    Core insulationPVC
  3. 3
    FillerPP filler
  4. 4
    ShieldBraid shield (C)
  5. 5
    SheathPVC

Technical parameters

Voltage class300 V
Core / pair design7 core
Conductor size0.75 mm²
Max DC resistance at 20 °C26.0 Ω/km
Screen / protectionNo overall screen, protected low-noise route
OD guide11 mm
Conductor materialClass 5 flexible copper conductor
Operating temperature−15 °C to +70 °C
Cable weight0.14 kg/m
Bend radius6 x OD during fixed installation
Outer sheathPVC
Routine test voltage2.0 kV a.c. 5 min

Ratings & materials

StandardVDE 0812
Voltage class300 V
UE Cable · China sales@uecable.com

Confirm quantity, colour, printing, packing length, delivery country and required test documents when sending an enquiry.

Request Quote