BS 7846 fire resistant armoured LSZH · 1C 50 mm²
Ordering reference BS 7846 fire resistant armoured LSZH · 1C 50 mm²
BS 7846
BS 7846 fire resistant armoured LSZH
Application
Emergency power · Life safety systems · Fire pumps · Critical infrastructure
Construction
- 1ConductorCopper conductor · 19 × Ø1.83 mm · IEC 60228 cl.2
- 2InsulationMica fire barrier with XLPE insulation
- 3BeddingPVC bedding
- 4ArmourGalvanised steel wire armour (SWA)
- 5SheathLSZH outer sheath
Technical parameters
Voltage class0.6/1 kV
Core layout1C
Cross-section50 mm²
ConductorCopper conductor
ArmourAluminium wire armour
Max DC resistance at 20 °C0.387 Ω/km
OD guide36 mm
Weight guide1.30 kg/m
Operating temperature−15 °C to +90 °C (fire-rated)
Bend radius12 x OD during installation
Outer sheathLSZH outer sheath
Current rating (guide)≈ 225 A (Cu, 1-core free air, 30 °C — IEC 60364-5-52 guide)
Routine test voltage3.5 kV a.c. 5 min
Ratings & materials
StandardBS 7846
Voltage class0.6/1 kV
UE Cable · China
sales@uecable.com
Confirm quantity, colour, printing, packing length, delivery country and required test documents when sending an enquiry.