Products产品中心 Standards标准库 Industries应用行业 Insights资讯 Generator线缆生成器 About关于我们
Request a Quote索取报价
← Back to BS 6622 XLPE AWA SWA PVC MV Armoured Cable
Cable Specification Sheet BS 6622 · Rev 01 · 2026-06

BS 6622 XLPE/AWA/SWA/PVC · Three core 400 mm²

Ordering reference  BS 6622 XLPE/AWA/SWA/PVC · Three core 400 mm²

BS 6622 BS 6622 XLPE/AWA/SWA/PVC

Application

Medium-voltage distribution · Substations · Utility feeders · Industrial direct burial

1234567
Indicative medium-voltage 3-core construction — aluminium conductor · screened, not to scale

Construction

  1. 1
    Conductor (per core)Aluminium conductor · 53 × Ø3.1 mm · IEC 60228 cl.2
  2. 2
    Core insulationXLPE
  3. 3
    FillerPP filler
  4. 4
    ShieldBraid shield (C)
  5. 5
    BeddingPVC bedding
  6. 6
    ArmourGalvanised steel wire armour (SWA)
  7. 7
    SheathPVC outer sheath

Technical parameters

Voltage class19/33 kV
Core layoutThree core
Cross-section400 mm²
ConductorAluminium conductor
ArmourSteel wire armour
Max DC resistance at 20 °C0.0778 Ω/km
OD guide91 mm
Weight guide8.9 kg/m
Operating temperature−40 °C to +90 °C
Bend radius15 x OD during installation
Outer sheathPVC outer sheath
Current rating (guide)≈ 512 A (Al, multicore clipped, 30 °C — IEC 60364-5-52 guide)
Routine test voltage66.5 kV a.c. (3.5 Uo, IEC 60502-2)

Ratings & materials

StandardBS 6622
Voltage class19/33 kV
UE Cable · China sales@uecable.com

Confirm quantity, colour, printing, packing length, delivery country and required test documents when sending an enquiry.

Request Quote